Reference Manual

Section 3: Installation

00809-0100-4102, Rev AA

May 2013

 

 

 

 

 

 

Figure 3-11. Installation examples

Liquid Service

Gas Service

Steam Service

 

A

 

 

 

A

A

 

 

A. Drain/vent valves

3.4.3Process connections

Coplanar or traditional process connection

Install and tighten all four flange bolts before applying pressure to avoid leakage. When properly installed, the flange bolts will protrude through the top of the sensor module housing. Do not attempt to loosen or remove the flange bolts while the transmitter is in service.

Flange adapters

Rosemount 2051DP and GP process connections on the transmitter flanges are 1/4–18 NPT. Flange adapters are available with standard 1/2–14 NPT Class 2 connections. The flange adapters allow users to disconnect from the process by removing the flange adapter bolts. Use plant-approved lubricant or sealant when making the process connections. Refer to Dimensional Drawings on page 101 for the distance between pressure connections. This distance may be varied ±1/4 in. (6.4 mm) by rotating one or both of the flange adapters.

To install adapters to a Coplanar flange, perform the following procedure:

Installation