2.7Review configuration data

The following is a list of factory default configurations that can be viewed by using the Field Communicator or AMS. Follow the steps below to review the transmitter configuration information.

Note

Information and procedures in this section that make use of Field Communicator fast key sequences and AMS assume that the transmitter and communication equipment are connected, powered, and operating correctly.

2.7.1Review pressure information

Fast Keys

2, 2, 2

To view pressure information:

1.From the Home screen, select 2: Configure.

2.Select 2: Manual Setup.

3.Select 2: Pressure.

4.Select from the corresponding number to view each field:

1Pressure

2Pressure Status

3Units

4Damping

2.7.2Review device information

Fast Keys

2, 2, 9

To view device information:

1.From the Home screen, select 2: Configure.

2.Select 2: Manual Setup.

3.Select 9: Device Information.

4.Select from the corresponding number to view each field:

1Identification

2Revisions

3Radio

4Sensor Information

5 Flange Information

6 Remote Seal