Section 6: Troubleshooting

 

Reference Manual

 

May 2013

 

 

00809-0100-4102, Rev AA

 

 

 

 

 

 

 

 

 

Device Status

Description

Recommended Action

 

 

 

 

 

 

LO Alarm

The primary variable has surpassed

1.

Verify that the process variable is within user

 

 

the user defined limit.

 

specified limits

 

 

 

2.

Reconfirm the user defined alarm limit

 

 

 

3.

If not needed, disable this alert

 

LO LO Alarm

The primary variable has surpassed

1.

Verify that the process variable is within user

 

 

the user defined limit.

 

specified limits

 

 

 

2.

Reconfirm the user defined alarm limit

 

 

 

3.

If not needed, disable this alert

 

Button Stuck

A buttons on the Electronics Board

1.

Check the buttons for obstructions

 

 

is detected as stuck in the active

 

 

 

 

position.

2.

Reset the device

 

 

 

 

 

 

3.

If the condition persists, replace the electronics

 

Simulation Active

The device is in simulation mode

1.

Verify that simulation is no longer required

 

 

and may not be reporting actual

 

 

 

 

information.

2.

Disable Simulation mode in Service Tools

 

 

 

 

 

 

3.

Reset the device

 

 

 

 

 

 

86

Troubleshooting

Page 98
Image 98
Emerson 00809-0100-4102 manual Check the buttons for obstructions