Section 2: Configuration
May 2013
Configuration
2051 Wireless pressure transmitter, damping only takes effect when the device is placed in high
power refresh mode and during calibration. In normal power mode, the effective damping is 0.
Note that when the dev ice is in h igh powe r refresh mode, battery power will be depleted rapidly.
Determine the appropriate damp setting based on the necessary response time, signal stability,
and other requirements of the loop dyna mics of your system. The dam ping value of your device
is user selectable from 0 to 60 seconds.

Damping with a Field Communicator

Enter desired Damping Value and select APPLY.

Damping with AMS Device Manager

Right click on the device and select Configure.
1. Select Manual Setup.
2. Within the Pressure Setup box, enter desired damping value and click Send.
3. Carefully read the warning and click Yes if it is safe to apply the changes.

2.9.3 Write protect

The Rosemount 2051 Wireless pressure transmitter has a software write protect security
feature.

Enabling write protect with a Field Communicator

Select Write Protec t to enable.

Enabling write protect with AMS Device Manager

Right click on device and select Configure.
1. Select Manual Setup.
2. Select the tab labeled Device Information.
3. Select Write Protec t to enable this feature.
2.10 Diagnostics and service
Diagnostics and service functions listed below are primarily for use after field installation. The
Transmitter Test feature is designed to verify that the transmitter is operating properly, and can
be performed either on the bench or in the field.
From the HOME screen, enter the fast key sequence
Device Dashboard Fast Keys 2, 2, 2, 4
From the HOME screen, enter the fast key sequence
Device Dashboard Fast Keys 2, 2, 7, 1