Section 2: Configuration

 

Reference Manual

May 2013

 

00809-0100-4102, Rev AA

 

 

 

 

 

 

Table 2-1. Variable Mapping

 

 

 

 

 

 

 

 

 

 

Classic Mapping

Scaled Variable Mapping

 

 

 

 

 

 

 

PV

Pressure

Scaled Variable

 

 

SV

Sensor Temperature

Pressure

 

 

TV

Electronics Temperature

Sensor Temperature

 

 

QV

Supply Voltage

Supply Voltage

 

 

 

 

 

 

Note

The variable assigned to the primary variable drives the output. This value can be selected as Pressure or Scaled Variable.

Re-mapping using a Field Communicator

From the HOME screen, enter the fast key sequence

Fast Keys

2, 2, 6, 1

 

 

Re-mapping using AMS Device Manager

Right click on the device and select Configure.

1.Select Manual Setup and click on the HART tab.

2.Assign Primary, secondary, tertiary and quaternary variables under Variable Mapping.

3.Click Send.

4.Carefully read the warning and click Yes if it is safe to apply the changes.

2.5.2Set range points

From the HOME screen, enter the fast key sequence

Fast Keys

2, 1, 1, 5

 

 

The Range Values command sets the lower and upper range values used for the percent of range measurement.

Note

Transmitters are shipped from Rosemount Inc. fully calibrated per request or by the factory default of full scale (span = upper range limit).

1.From the Home screen, select 2: Configure

2.Select 1: Guided Setup

3.Select 1: Basic Setup

4.Select 5: Range Values

14

Configuration

Page 26
Image 26
Emerson 00809-0100-4102 manual Set range points, Re-mapping using a Field Communicator, Re-mapping using AMS Device Manager