21
Reference Manual
00809-0100-4102, Rev AA
Section 2: Configuration
May 2013
Configuration
2.7.3 Review radio information
To vie w ra dio inf orm atio n:
1. From the Home screen, select 1: Overview.
2. Select 7: Device Information.
3. Select 3: Radio.
4. Select from the corresponding number to view each field:
2.7.4 Review operating parameters
The pressure output value in both engineering units and percent of range will reflect the applied
pressure even when the applied pressure is outside of the configured range as long as the
applied pressure is between the upper and lower range limit of the transmitter. For example, if a
Range 2 2051T (LRL = 0 psi, URL = 150 psi) is ranged from 0 to 100 psi, an applied pressure of
150psi will return a % of range output of 150% and an engineering output of 150 psi.
To vie w th e Operating Parameters menu:
1. From the Home screen, select 3: Service Tools.
2. Select 2: Variables.
The Operating Parameters menu displays the following information pertaining to the device:
1. Process
Pressure
Percent of Range
Last Update Time
Scaled Variable
Enter Fast Update Mode
2. Device
Sensor Temperature
Supply Voltage
Fast Keys 1, 7, 3
1Manufacturer
2Device Type
3Device Revision
4Software Revision
5Hardware Revision
6Transm it Powe r Le vel
7Minimum Update Rate
Fast Keys 3, 2