Reference Manual

Section 2: Configuration

00809-0100-4102, Rev AA

May 2013

2.7.3Review radio information

Fast Keys

1, 7, 3

To view radio information:

1.From the Home screen, select 1: Overview.

2.Select 7: Device Information.

3.Select 3: Radio.

4.Select from the corresponding number to view each field:

1Manufacturer

2 Device Type

3 Device Revision

4 Software Revision

5 Hardware Revision

6 Transmit Power Level

7 Minimum Update Rate

2.7.4Review operating parameters

Fast Keys

3, 2

The pressure output value in both engineering units and percent of range will reflect the applied pressure even when the applied pressure is outside of the configured range as long as the applied pressure is between the upper and lower range limit of the transmitter. For example, if a Range 2 2051T (LRL = 0 psi, URL = 150 psi) is ranged from 0 to 100 psi, an applied pressure of 150 psi will return a % of range output of 150% and an engineering output of 150 psi.

To view the Operating Parameters menu:

1.From the Home screen, select 3: Service Tools.

2.Select 2: Variables.

The Operating Parameters menu displays the following information pertaining to the device:

1.Process

Pressure

Percent of Range

Last Update Time

Scaled Variable

Enter Fast Update Mode

2.Device

Sensor Temperature

Supply Voltage

Configuration

21

Page 33
Image 33