Section 2: Configuration

00809-0100-4102, Rev AA

May 2013

a.When configuring for level applications, select Linear under Select Scaled data options.

b.When configuring for flow applications, select Square Root under Select Scaled data options.

DP Level Example

Figure 2-3. Example tank

A

B

D

H L

C

A. 230 in.

B. 200 in.

C. 12 in.

D. 0.94 sg

A differential transmitter is used in a level application. Once installed on an empty tank and taps vented, the process variable reading is -209.4 inH2O. The process variable reading is the head pressure created by fill fluid in the capillary. Based on Table 2-2 on page 2-17, the Scaled Variable configuration would be as follows:

Table 2-2. Scaled Variable Configuration for Tank Application

Scaled Variable units:

inch

 

 

Scaled data options:

linear

 

 

Pressure value position 1:

0 inH2O

Scaled Variable position 1:

12 in.

 

 

Pressure value position 2:

188 inH2O

Scaled Variable position 2:

212 in.

 

 

Linear offset:

-209.4 inH2O

DP Flow example

 

A differential pressure transmitter is used in conjunction with an orifice plate in a flow

 

 

application where the differential pressure at full scale flow is 125 inH2O. In this particular

 

Configuration

application, the flow rate at full scale flow is 20,000 gallons of water per hour. It is highly

17

 

Page 29
Image 29