Reference Manual

 

 

Section 5: Troubleshooting

00809-0100-4102, Rev AA

 

 

May 2013

 

 

 

 

 

 

 

 

 

Device Status

 

Description

Recommended Action

 

 

 

 

 

Pressure has

 

The sensor has exceeded the

1.

Check process for possible saturation condition

Exceeded Limits

 

maximum measurement range.

 

 

 

 

 

 

2.

Verify that the appropriate sensor was chosen for the

 

 

 

 

application

 

 

 

3.

Reconfirm sensor configuration

 

 

 

4.

Reset the device

 

 

 

5.

Replace the sensor

Electronics

 

The electronics temperature has

1.

Verify environmental temperature is within the

Temperature has

 

exceeded the transmitter's

 

transmitter’s range

Exceeded Limits

 

maximum range.

 

 

 

 

 

 

2.

Remote mount the transmitter away from process

 

 

 

 

and environmental conditions

 

 

 

3.

Reset the device

 

 

 

4.

If the condition persists, replace the electronics

Supply Voltage Low

 

The supply voltage is low and may

1.

Replace the Power Module

 

 

soon affect broadcast updates.

 

 

 

Database Memory

 

The device has failed to write to

1.

Reset the device

Warning

 

the database memory. Any data

 

 

 

 

 

written during this time may have

2.

Reconfirm all configuration items in the device

 

 

been lost.

 

 

 

 

 

 

 

 

3.

If logging dynamic data not needed, this advisory

 

 

 

 

can be safely ignored

 

 

 

4.

If the condition persists, replace the electronics

Configuration Error

 

The device has detected a

1.

Click on details for more information

 

 

configuration error based on a

 

 

 

 

 

change to the device.

2.

Correct the parameter that has a configuration error

 

 

 

 

 

 

3.

Reset the device

 

 

 

4.

If the condition persists, replace the electronics

HI HI Alarm

 

The primary variable has surpassed

1.

Verify that the process variable is within user

 

 

the user defined limit.

 

specified limits

 

 

 

2.

Reconfirm the user defined alarm limit

 

 

 

3.

If not needed, disable this alert

HI Alarm

 

The primary variable has surpassed

1.

Verify that the process variable is within user

 

 

the user defined limit.

 

specified limits

 

 

 

2.

Reconfirm the user defined alarm limit

 

 

 

3.

If not needed, disable this alert

 

 

 

 

 

 

Troubleshooting

85

Page 97
Image 97
Emerson 00809-0100-4102 manual Reference Manual Troubleshooting, Check process for possible saturation condition