Extreme Networks 12800 Series manual 100

Models: 12800 Series

1 160
Download 160 pages 31.56 Kb
Page 100
Image 100

Installing Power Supply Units

Power Supply Cords

Each Extreme Networks 325 W AC PSU is shipped with a 110 V AC UL Listed power cord.

All power supply cords provided by Extreme Networks are designed for use in the United States and Canada only. Power supply cords for use outside of North America are typically provided by a third-party distribution center and must meet the following requirements:

Power supply cords must be agency certified for country of use.

Power supply cords must contain an IEC 320 C13 connector for insertion into the IEC 320 C14 receptacle on the PSU.

Power supply cords must contain an appropriately rated and approved wall plug applicable to the country of installation.

Power supply cords must be less than 5 m long.

Wire size must be a minimum of 18 AWG (0.82 mm2) copper-stranded.

WARNING!

Make sure that the source outlet is properly grounded before plugging the AC power cord into the Extreme Networks 325 W AC PSU.

Fuse

The Extreme Networks 325 W AC PSU line is fused. This is not a field operator replaceable fuse. In the event of failure, immediately return the Extreme Networks 325 W AC PSU for a complete replacement.

WARNING!

Field operators must not attempt to configure or replace fuses in Extreme Networks 325 W AC PSUs! In the event of failure, immediately return the defective Extreme Networks 325 W AC PSU for a complete replacement.

100

BlackDiamond 12800 Series Switches Hardware Installation Guide

 

 

Page 100
Image 100
Extreme Networks 12800 Series manual 100