Site Preparation
NOTE
As with all electrical equipment, product lifetimes degrade with increased temperature. If possible, temperatures should be kept at approximately 78° F (25° C) or lower.
Humidity
To maximize equipment life, keep operating humidity between 50% and 70% relative humidity (non- condensing) during typical operation. The equipment can operate between 10% and 95% relative humidity
BlackDiamond Family Chassis Spacing Requirements
Because of
●Leave a minimum of one empty
or
●Place patch panels between two sets of three adjacent BlackDiamond switches. A patch panel does not require any power and does not generate any heat.
NOTE
Up to five adjacent switches will continue to function without safety concerns. However, product lifetime may degrade with continued exposure to high temperatures in close proximity and long term reliability may be compromised.
Airflow Requirements
To ensure proper airflow through a BlackDiamond 12800 series switch, refer to the following recommendations:
●BlackDiamond 12800 series switches require a minimum of 1.5 inches (4 cm) around both the left and right sides of the chassis from any cabinet wall or other obstruction for proper airflow.
●Air temperature measured approximately 1 inch (2.5 cm) from the fan inlet should be less than 104 °F (40 °C).
In the BlackDiamond 12800 series switches, airflow through the power supplies is independent of the airflow through the modules as shown in Figure 20.
44 | BlackDiamond 12800 Series Switches Hardware Installation Guide |
|
|