Extreme Networks 1200 W DC PSU
Minimum Software Required
You must be running ExtremeWare XOS version 11.3 or later for the system to recognize the DC PSU.
Pre-Installation Requirements
You need the following tools and equipment to install or remove a 1200 W DC PSU:
●
●Input DC power cable (provided with the DC PSU)
●
●Thermal protective gloves (required for removal)
Installing the DC Wiring
The input DC cable for the DC PSU is supplied with the 1200 W DC PSU (see Figure 40); you must use this cable with the DC PSU.
Figure 40: Input DC Power Cable for the 1200 W DC PSU
Lock
Return
Ground
Black: Return
Blue:
Green/yellow:
Ground
10 ft.
EX_135
Each 1200 W DC PSU must be powered by a 50 A dedicated power source that delivers
The input DC cable has an input connector on one end and precut wire on the other end that goes to the DC power source. The connector end has a locking mechanism that locks onto the DC PSU to prevent accidental removal of the input DC cable.
If necessary, use appropriate termination lugs for 8 AWG (10 mm2)
The blue termination
BlackDiamond 12800 Series Switches Hardware Installation Guide | 75 |
|
|