Hardware installation

AC source related power supply configuration and system load limits

The system configuration and load is limited by the number of AC mains power sources available as indicated in the following table.

Number

AC redundant systems

AC non-redundant systems

of power

(requires 2 AC sources)

(connected to 1 AC source)

supply

 

 

 

 

Max. DC

Installation

Max. DC

Installation

modules

loading to

requirements

loading for AC

requirements

installed

support AC

 

non-redundant

 

 

 

 

 

redundancy

 

systems

 

 

 

 

 

 

2

830W

2 PSUs

1580W

2 PSUs

 

 

connected to

 

connected to

 

 

mains (1+1)

 

mains (1+1)

 

 

 

 

 

3

N/A

N/A

2320W

3 PSUs

 

 

 

 

connected to

 

 

 

 

mains (2+1)

4

1580W

2 PSUs

2320W

4 PSUs

 

 

connected to

 

connected to

 

 

mains2 PSUs

 

mains (3+1)

 

 

connected to

 

 

 

 

an isolated AC

 

 

 

 

source

 

 

 

 

e.g. UPS (2+2)

 

 

Table 4: System power supply configuration and system load limits

Installation in PRIMECENTER/Datacenter rack

Please follow the installation requirements for connection to the mains described in the rack manuals.

RX600 S6

Operating Manual

51