GE GFK-0804B manual IBM Compiler Basic

Models: GFK-0804B

1 160
Download 160 pages 24.24 Kb
Page 100
Image 100

B

IBM Compiler BASIC

H

Function

: Read Register

 

 

 

Call

: int

BASRreg (port%, memtype%, addr%, count%, buf%(0),

 

 

 

 

status%);

 

 

 

Inputs

: int

port;

/* 0±COM1, 1±COM2

*/

 

 

int

memtype;

/* 0±IR, 1±OR, 2±R

*/

 

 

int

addr;

/* Adrs. of the 1st register to read

*/

 

 

int

count;

/* Number of words to read

*/

 

Return

: int

*buf;

/* Data read

*/

 

 

int

status;

/* Error status±0: Normal

*/

H

Function

: Write Register

 

 

 

Call

: int

BASWreg (port%, memtype%, addr%, count%, buf%(0),

 

 

 

 

status%);

 

 

 

Inputs

: int

port;

/* 0±COM1, 1±COM2

*/

 

 

int

memtype;

/* 1±OR, 2±R

*/

 

 

int

addr;

/* Adrs. of the 1st register to write

*/

 

 

int

count;

/* Number of words to write

*/

 

 

: int

*buf;

/* Data to write

*/

 

Return

int

status;

/* Error status±0: Normal

*/

H

Function

: Read Bit

 

 

 

 

Call

: int

BASRbit (port%, memtype%, addr%, count%, buf$,

 

 

 

 

status%);

 

 

 

Inputs

: int

port;

/* 0±COM1, 1±COM2

*/

 

 

int

memtype;

/* 0±DI, 1±DO, 4±C

*/

 

 

int

addr;

/* Adrs. of the 1st discrete to read

*/

 

 

int

count;

/* Number of bits to read

*/

 

Return

: char

*buf;

/* Data read

*/

 

 

int

status;

/* Error status±0: Normal

*/

H

Function

: Write Bit

 

 

 

 

Call

: int

BASWbit) (port%, memtype%, addr%, count%, buf$,

 

 

 

 

status%);

 

 

 

Inputs

: int

port;

/* 0±COM1, 1±COM2

*/

 

 

int

memtype;

/* 1±DO, 4±C

*/

 

 

int

addr;

/* Adrs. of the 1st discrete to write

*/

 

 

int

count;

/* Number of bits to write

*/

 

 

char

*buf;

/* Data to write

*/

 

Return

int

status;

/* Error status±0: Normal

*/

B-12

Micro PLC Programmer's Guide ± Aptil 1994

GFK-0804B

Page 100
Image 100