GE GFK-0804B manual Communications Memory Types and Addresses, Communications Parameters

Models: GFK-0804B

1 160
Download 160 pages 24.24 Kb
Page 91
Image 91

B

Communications Memory Types and Addresses

I/O Memory Addresses

Type

Code

Max

Address Range (hex)

DiscreteInput

I

256

0000 ± 00FF

 

 

 

 

Discrete Output

O

256

0100 ± 01FF

 

 

 

 

Forced Discrete Input

FI

256

0200 ± 02FF

 

 

 

 

Forced Discrete Output

FO

256

0300 ± 03FF

 

 

 

 

Internal Coil

C

1024

0400 ± 07FF

Registers

(includes the next two items)

AnalogInput

AnalogOutput

InternalRegisters

IR

OR

R

256

512

0000 ± 01FE *

0200 ± 03FE *

0400 ± 07FE *

*Byte address with Least Significant Bit always 0.

Special Registers

Registers 501 to 512 are reserved. Registers 510 to 512 are used for communications setup.

Register

510

511

512

Function

Protocol

StationAddress

Baud rate

Description

0 = Micro PLC (default)

1 = RTU

1 (default) to 247

0 = 300

1 = 600

2 = 1200

3 = 2400

4 = 4800

5 = 9600

Communications Parameters

 

Baud Rate

9600 (default)

 

 

Data Bits

8

 

 

Stop Bit

1

 

 

Parity

None

 

GFK±0804B

Appendix B Micro PLC Protocol

B-3

Page 91
Image 91