Skip/End Coil Pair

The Skip/End coil pair can be used to cause one or more outputs in the program to stay in their current state (1 or 0), regardless of the state of any inputs or other conditional logic to those outputs. The rungs with the outputs to be controlled must be located between the Skip coil and its paired End coil in the program.

In the example below, the Skip and End coil control the states of outputs O17 and O18. While the Skip coil receives power flow from its conditional logic (in the example, it is contact I1), all output coils within the Skip/End pair hold their last states.

Programming Software Instructions

If you are using the programming software, refer to the instructions on page 4-11.

Example and HHP Instructions

Skip

SKIP

 

Ladder Diagram

I1

 

 

SKIP

I2

O17

I3

O18

END

Timing Diagram

Input I1

Input I2

Output O17

Input I3

Output O18

End

 

 

END

 

 

 

 

 

 

 

46025

 

Hand-held Programmer

START

 

 

 

I1

OUT

 

 

 

More MENU F2 (SKIP)

START

 

 

 

I2

OUT

 

 

 

O17

START

F3 (NOT) I3

OUT

 

 

 

O18

START

 

 

 

More MENU F3 (END)

OUT

 

 

 

This is a Skip to END operation. When input I1 is 0, the Skip command is not performed.

When input I1 is 1, all outputs till END are on hold, and are not affected by input conditions.