GE GFK-0804B manual General Programming Software Instructions for Coils, Using Coil Pairs

Models: GFK-0804B

1 160
Download 160 pages 24.24 Kb
Page 52
Image 52

4

Coils

The Micro PLC instruction set includes the following coils:

±(

Coil. The basic type of program output.

±(SET)±

Set coil. Used to set a specified reference to 1.

±(RST)±

Reset coil. Used to reset the same specified reference to 0.

±(MCR)±

Master Control Relay. Used to set a group of outputs to 0.

±(SKIP)±

Skip. Used to cause a group of outputs to hold last state.

±(END)±

End of MCR or Skip

Using Coil Pairs

The following types of coils must always be used in pairs. If one of these instructions is used in the program, the paired instruction must also exist somewhere in the program.

SET

RST

Set and Reset

MCR

END

Master Control Relay and End MCR

SKIP

END

Skip (rungs) to rung containing End

General Programming Software Instructions for Coils

1. Select ±( )±

(F3), then use the assigned function key(s) to select an output type:

±(

(F1)

Coil

±(SET)±

(F2)

Set coil

±(RST)±

(F3)

Reset coil

±(MCR)±

(F4)

Master Control Relay

±(SKIP)±

(F5)

Skip

±(END)±

(F6)

End of MCR or Skip

The selected coil type appears at the end of the rung:

2.Enter an appropriate address. For a coil, enter an address in output (O) or internal coil (C) memory. For example, C0001. You don't need to enter leading zeros.

3.Press the Enter key. The memory type and address appear:

If you want to change the memory type and address, press the Enter key. A cursor appears next to the address. Type in the new memory type and address. Press the Enter key again to accept the new entry.

GFK-0804B

Chapter 4 The Micro PLC Instruction Set

4-11

Page 52
Image 52