Set/Reset Coil Pair

The Set/Reset coil pair can be used to control the state of an associated reference. The Set coil sets the reference to 1. The reference (O17 in the example below) STAYS set to 1 until it is reset to 0 by the Reset coil. Notice that the Set and Reset coil are programmed with the same associated reference; that of reference being controlled.

In the example below, the Set coil and Reset coil are shown in adjoining rungs of logic. That is not necessary, however.

Programming Software Instructions

If you are using the programming software, refer to the instructions on page 4-11.

Example and HHP Instructions

Set

SET

 

Ladder Diagram

I1

O17

 

SET

I2

O17

 

RST

Timing Diagram

Input I1

Input I2

Output O17

Reset

 

 

RST

 

 

46023

 

 

 

 

 

 

 

 

 

 

 

Hand-held Programmer

 

START

 

 

 

 

 

I1

OUT

F2 (SET)

O17

START

 

 

 

 

 

I2

OUT

F2(RESET)

O17

This is a flip-flop operation. Input I1 sets output O17 to 1. Output O17 remains 1 even if I1 changes to 0. Output O17 is only reset to 0 when I2 is activated.

When both I1 and I2 are ON, the last occurrence in the scan (RST in this case) takes precedence.

GFK-0804B

Chapter 4 The Micro PLC Instruction Set

4-13