Application #2: Power Up One Shot (Start±up Protection)

This logic uses a special purpose coil called the Start±Up Scan Coil to provide protection in the event of power loss or stoppage in a program. The FLIP/FLOP program shown in Application 1 has been modified for this application. A typical ladder logic is shown be- low.

Rung 1

C1019C1 +±±±±+±±±±±±±+±±±±±±±+±±±+±±±±±±±+±±±±±±±+±(SET)±

Rung 2

I2

C1

+±±±±+±±±±±±±+±±±±±±±±±±+±±±±±±±+±±±±±±±+±(RST)±

PB2

 

 

Rung 3

 

 

I1

C1

C2

+±±+±±+±±/±±+±±±±±±+±±±±±±±±±+±±±±±±±±±±+±±()±±

PB1

 

 

 

Rung 4

 

 

 

C2

O1

C1

O1

+±± ±±+±±/±±+±±±±±±±+±±±±±±±+±±/±±±±±±+±±( )±±

C2

O1

+±±/±±+±± ±±+

In the logic above, the start±up scan coil C1019 is used to set coil C1 in rung 1. Coil C1019 produces a positive output for a single program cycle when power is first applied or when the PLC is first put into RUN mode from a STOP/PROGRAM condition. At all other times, C1019 is off. Because C1 in rung 1 is defined as being in a set condition, C1 turns on when C1019 turns on and will remain on until a reset condition is activated. Push button 2 (PB2) in rung 2 activates the reset condition in this ladder.

In rungs 3 and 4, N.C. contact C1 is placed immediately before the output coils. These contacts are open when C1 is set, which prevents either rung from being executed until PB2 is pushed. Once C1 is reset, both N.C. contacts return to their base states and the program performs normally.