TROUBLESHOOTING & REPAIR

ROTOR “FLASHING” CIRCUIT TEST (continued)

FIGURE F.10 - IDLER P.C. BOARD PIN ASSIGNMENTS

Return to Section TOC

Return to Master TOC

TO

CURRENT

TRANSFORMER

J2J1

WP125 IDLER

M17578

204(BLACK)

202A (RED)

208(BROWN)

209(BROWN)

200A (WHITE)

16(BLACK)

9B (BROWN)

14(WHITE)

203(RED)

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

WARNING

MOVING PARTS can injure.

Keep away from moving parts.

ENGINE EXHAUST can kill.

Use in open, well ventilated areas or vent exhaust to the outside.

5.Start the engine and run it at High Idle (3700 - 3800 RPM).

6.The DC ammeter should read between 0.22 and 0.30 amps.

7.If the DC ammeter reads 0.0 amps, check for flashing voltage between lead #202B from the brush holder and case ground (lead #201). See Figure F.8 and the Wiring Diagram. Normal flashing voltage is 2.05 VDC.

8.If normal flashing voltage is present, per- form the Rotor Resistance Test. Also be sure that all #201 leads have continuity (zero ohms) to case ground.

9.If normal flashing voltage is NOT present from lead #202 to case ground, check the continuity of lead #202 to the idler P.C. board. Also check the continuity of lead #14 from the engine magneto to the P.C. board. See Figure F.10 and the Wiring Diagram.

10.If the above continuity checks are good, run the engine at high idle (3700 - 3800 RPM). Check for an AC voltage from lead #14 to case ground. Normal is 3.30 VAC. If a low or zero AC voltage is indicated, the engine magneto may be faulty. Replace.

11.If the AC voltage reading from step 9 is normal, the idler P.C. board may be faulty. Replace the idler P.C. board.

12.After the problem has been repaired, replace the top cover on the control box. Tighten the 8 sheet metal screws with the 5/16" nut driver.

WELDANPOWER 125

Page 63
Image 63
Lincoln Electric SVM 113-A service manual WP125 Idler