8 Minute Lockout

Section 6

Electrical System

 

 

QF2200

Automatic Shut-Off

L1

L2

GROUND

An 8 minute lockout starts when the compressor de-energizes. When the ice drops away from the bin level probe the ice machine will begin an initial start-up cycle, provided the “8 minute lockout” has expired.

8 Minute Lockout

The bin level light will flash until the 8 minute lockout expires. After the 8 minute lockout time can be overridden by moving the ON/OFF/ CLEAN toggle switch for ICE to OFF and back to ICE.

 

 

LIQUID LINE

 

RELAY

 

(54)

SOLENOID

(53)

K2

 

 

 

RELAY

CENTRIFUGAL

 

K1

 

 

SWITCH

 

(25)

 

 

 

 

 

 

 

7 AMP

 

INTERNAL

 

 

FUSE

 

 

 

 

(65)

OVERLOAD

START

 

 

 

 

 

 

 

 

 

RELAY

 

RUN

 

RELAY K4

 

 

 

K3

 

 

 

 

 

GEARMOTOR

 

(52)

WATER FLOAT

 

 

 

 

VALVE COIL

 

 

 

 

 

(56)

 

 

(22)

 

 

 

 

(51)

(55)

 

 

 

 

 

 

 

DUMP VALVE

 

 

 

 

COIL

 

 

 

 

 

 

 

SV3048

Automatic Shut-Off(Until Ice No Longer Contacts Bin Level Probe)

Toggle Switch

ICE

 

 

Bin Level Probe

CLOSED ( Ice Contacting probe)

 

 

Control Board Relays

 

 

 

 

#1

Liquid Line Solenoid Valve

OFF

 

 

 

#2

Dump Valve

OFF

 

 

 

#3

Gear Motor

OFF

 

 

 

#$

Water Float Valve Solenoid Coil

OFF

 

 

 

Part No. 80-1214-3