Manitowoc Ice QF2300, QF0800, QC0700 Refrigeration System, Section, Analyzing Suction Pressure

Models: QF2200 QF0400 QC0700 QF0800 QF2300

1 150
Download 150 pages 297 b
Page 130
Image 130
ANALYZING SUCTION PRESSURE

Refrigeration System

Section 7

 

 

ANALYZING SUCTION PRESSURE

NOTE: Analyze discharge pressure before analyzing suction pressure. High or low discharge pressure may be causing high or low suction pressure.

Suction Pressure High Checklist

Possible Cause

Check/Correct

 

 

Improper installation

See “Installation/Visual Inspection Checklist”

 

 

Discharge pressure

Discharge pressure is too high, and is affecting suction pressure

 

(See “Freeze Cycle Discharge Pressure High Checklist”

 

 

Improper refrigerant charge

Overcharged

 

Wrong type of refrigerant

 

Non condensables in system

 

 

Other

Non-Manitowoc components in system

 

TXV flooding (check bulb mounting)

 

Defective compressor

 

 

Suction Pressure Low Checklist

 

Possible Cause

Check/Correct

 

 

Improper installation

See “Installation/Visual Inspection Checklist”

 

 

Discharge pressure

Discharge pressure is too low, and is affecting suction pressure (See “Freeze Cycle

 

Discharge Pressure Low Checklist”)

 

 

Improper refrigerant charge

Undercharged

 

Wrong type of refrigerant

 

 

Other

Non-Manitowoc components in system

 

Restricted/plugged liquid line drier

 

Restricted/plugged tubing in suction side of refrigeration system

 

Expansion valve starving

 

No water or insufficient pressure

 

Defective compressor

 

Moisture in refrigeration system

 

Dirty Evaporator

 

Defective Fan Cycle Control

 

RFC2085/RFC2385 Only - Defective Head Pressure Control

 

 

NOTE: Do not limit your diagnosis to only the items listed in the checklists.

7-8

Revised 8/2003

Part No. 80-1214-3

 

 

Page 130
Image 130
Manitowoc Ice QF2300, QF0800 Refrigeration System, Section, Analyzing Suction Pressure, Suction Pressure High Checklist