Manitowoc Ice QC0700 Section, Electrical System, 6-35, QF2300 Automatic Shut-Off, Minute Lockout

Models: QF2200 QF0400 QC0700 QF0800 QF2300

1 150
Download 150 pages 297 b
Page 97
Image 97
6-35

Section 6

Electrical System

 

 

QF2300

Automatic Shut-Off

An 8 minute lockout starts when the compressor de-energizes. When the ice drops away from the bin level probe the ice machine will begin an initial start-up cycle, provided the “8 minute lockout” has expired.

8 Minute Lockout

The bin level light will flash until the 8 minute lockout expires. After the 8 minute lockout time can be overridden by moving the ON/OFF/ CLEAN toggle switch for ICE to OFF and back to ICE.

L1

GROUND

 

C1

C2

L2

 

 

 

 

 

 

 

 

 

 

 

LIQUID LINE

 

 

 

(54)

SOLENOID

(53)

 

RELAY

 

 

 

(91)

 

 

 

 

K2

 

EQUALIZATION

 

 

 

(58)

SOLENOID

(57)

 

 

RELAY

 

 

 

 

 

 

 

(25)

K1

 

 

 

 

7 AMP

 

CENTRIFUGAL

(22)

 

 

 

SWITCH

 

FUSE

 

INTERNAL

 

 

 

 

(65)

OVERLOAD

START

 

 

 

 

 

 

 

 

 

 

 

 

RELAY

 

RUN

 

 

RELAY K4

 

 

 

 

K3

 

 

 

 

 

GEARMOTOR

 

 

 

 

 

 

 

WATER FLOAT

 

 

 

(52)

VALVE

(56)

 

 

 

 

 

 

 

(22)

 

 

 

 

 

 

 

(55)

 

 

 

(51)

 

 

 

 

DUMP VALVE

SV2113

Automatic Shut-Off(Until Ice No Longer Contacts Bin Level Probe)

Toggle Switch

ICE

Bin Level Probe

CLOSED ( Ice Contacting probe)

Control Board Relays

 

#1

Liquid Line Solenoid Valve

OFF

#2

Dump Valve

OFF

#3

Gear Motor

OFF

#$

Water Float Valve Solenoid Coil

OFF

Part No. 80-1214-3

Revised 8/2003

6-35

 

 

Page 97
Image 97
Manitowoc Ice QC0700, QF0800, QF0400, QF2200 Section, Electrical System, 6-35, QF2300 Automatic Shut-Off, Minute Lockout