QF2300

Electrical System

Section 6

 

 

QF2300

Automatic Shut-Off

3B. WATER DRAIN

To allow water to drain from the evaporator, the dump valve energizes for 90 seconds, then de-energizes.

An 8 minute lockout starts when the compressor de-energizes. When the ice drops away from the bin level probe the ice machine will begin an initial start-up cycle, provided the “8 minute lockout” has expired.

L1

GROUND

 

C1

C2

L2

 

 

 

 

 

 

 

 

 

 

 

LIQUID LINE

 

 

 

 

(54)

SOLENOID

 

 

RELAY

 

(53)

 

(91)

 

 

 

 

K2

 

EQUALIZATION

 

 

 

 

(58)

SOLENOID

(57)

 

 

RELAY

 

 

 

 

 

 

 

(25)

K1

 

 

 

 

 

 

 

 

 

7 AMP

 

CENTRIFUGAL

(22)

 

 

 

SWITCH

 

FUSE

 

INTERNAL

 

 

 

 

(65)

OVERLOAD

START

 

 

 

 

 

 

 

 

RELAY

 

RUN

 

 

RELAY K4

 

 

 

 

K3

 

 

 

 

 

GEARMOTOR

 

 

 

 

 

 

 

WATER FLOAT

 

 

 

(52)

VALVE

(56)

 

 

 

 

 

 

 

(22)

 

 

 

 

 

 

 

(55)

 

 

 

(51)

 

 

 

 

DUMP VALVE

 

 

SV2112

 

 

3B. Water Drain (90 Seconds)

Toggle Switch

ICE

Bin Level Probe

CLOSED ( Ice Contacting probe)

Control Board Relays

 

#1

Liquid Line Solenoid Valve

OFF

#2

Dump Valve

ON

#3

Gear Motor

OFF

#$

Water Float Valve Solenoid Coil

OFF

6-34

Revised 8/2003

Part No. 80-1214-3

 

 

Page 96
Image 96