Manitowoc Ice QF2300, QF0800 Electrical System, Section, 6-22, QF2200 Automatic Shut-Off

Models: QF2200 QF0400 QC0700 QF0800 QF2300

1 150
Download 150 pages 297 b
Page 84
Image 84
QF2200

Electrical System

Section 6

 

 

QF2200

Automatic Shut-Off

3A. ICE RUN OUT

L1

L2

GROUND

LIQUID LINE

Ice will build up in the bin until it contacts the bin level probe. After ice contacts the bin level probe for 30 continuous seconds the liquid line solenoid valve de-energizes. To allow excess ice to run out, the gear motor and the water float valve solenoid remain energized for an additional 4 minutes, then de-energize.

RELAY

 

(54)

SOLENOID

(53)

K2

 

 

 

RELAY

CENTRIFUGAL

 

K1

 

 

SWITCH

 

(25)

 

 

 

 

 

 

 

7 AMP

 

INTERNAL

 

 

FUSE

 

 

 

 

(65)

OVERLOAD

START

 

 

 

 

 

 

 

 

 

RELAY

 

RUN

 

RELAY K4

 

 

 

K3

 

 

 

 

GEARMOTOR

 

 

 

 

(52)

WATER FLOAT

 

 

 

 

VALVE COIL

(56)

 

 

 

 

 

 

(22)

 

 

 

 

(51)

(55)

 

 

 

 

 

 

 

DUMP VALVE

 

 

 

 

COIL

 

 

 

 

 

 

 

SV3047

 

 

3A. ICE RUN OUT (45 Seconds)

 

 

 

Toggle Switch

 

ICE

 

 

 

Bin Level Probe

 

CLOSED ( Ice Contacting probe)

 

 

 

Control Board Relays

 

 

 

 

 

 

#1

Liquid Line Solenoid Valve

 

OFF

 

 

 

 

#2

Dump Valve

 

OFF

 

 

 

 

#3

Gear Motor

 

ON

 

 

 

 

#$

Water Float Valve Solenoid Coil

 

ON

 

 

 

 

6-22

Revised 8/2003

Part No. 80-1214-3

 

 

Page 84