Section 2 | Installation Instructions |
|
|
Electrical Service
GENERAL
!Warning
All wiring must conform to local, state and national codes.
VOLTAGE
The maximum allowable voltage variation is ±10% of the rated voltage on the ice machine model/serial number plate at
!Warning
The ice machine must be grounded in accordance with national and local electrical codes.
FUSE/CIRCUIT BREAKER
A separate fuse/circuit breaker must be provided for each ice machine. Circuit breakers must be H.A.C.R. rated (does not apply in Canada).
QF400 115/60/1 ice machines are factory
MINIMUM CIRCUIT AMPACITY
QC700/QF800/QF2200/QF2300 Only
The minimum circuit ampacity is used to help select the wire size of the electrical supply. (Minimum circuit ampacity is not the ice machine’s running amp load.) The wire size (or gauge) is also dependent upon location, materials used, length of run, etc., so it must be determined by a qualified electrician.