Fan and Deflector Requirements

Forced-air cooling for up to four rack-mounted enclosures can be provided by fans and a deflector, mounted below the enclosures, to provide passive, bottom-entry rear exhaust and upward-forced, front- entry cooling air. Refer to Figure 1-6. The airflow requirement is 80 CFM (2266230 CCM).

For example, three fans rated 117 CFM (202176 CCM) at a static pressure of 0 inches of water provide enough airflow, when cooling four enclosures. The deflector ensures that hot air from equipment below the enclosures does not mix with enclosure-cooling air. The cabinet must have venting at the top or rear to let exhaust air escape.

Unit 2

Fan Chassis 2

Unit 1

AccessWay

AccessWay

AccessWay

AccessWay

Fan Chassis 1

Figure 1-6. Cabinet ArrangementThree or More Enclosures