3460 Fast’R

Connecting the AccessWay to DC Power Supply (continued)

Step

 

Action

 

 

6.

Optionally, connect a remote alarm monitoring device to the

 

AccessWay, to alert you to a fault in the DC output voltage.

 

a)

Determine whether you want the alarm relay contacts

 

 

open or closed when AccessWay output voltages are

 

 

within normal operating range. The default setting is

 

 

Normal Open.

 

b)

Optionally, reverse this setting: at the front of the

 

 

AccessWay, loosen a power module’s captive screws

 

 

and pull the power module out of the AccessWay. Set

 

 

the jumper to the Normal Closed position

 

 

(Figure 1-12). Replace the power module in the

 

 

AccessWay. Tighten the captive screws that secure it.

 

c)

Connect two lengths of wire from the alarm monitor

 

 

device terminals to the ALARM 1 terminals on the

 

 

back of the AccessWay.

 

 

7.

If you disconnected the power terminal block from the rear of

 

the AccessWay unit, replace it.

 

 

8.

Attach the cable clamp (Figure 1-13; provided with the

 

AccessWay) to the wire bundle at the rear of the AccessWay.

 

Leave a service loop of at least 8 cm between the clamp and the

 

terminal block, and secure the clamp to the screw at the left of

 

the terminal block.

 

Ensure that any strain is relieved from the cable terminals, and

 

that the power terminal block is easily accessible should you

 

need to remove it quickly in an emergency.

 

 

9.

Apply DC power to the AccessWay.

 

Verify that the LEDs near the bottom of the power module(s) are

 

lit. The LEDs indicate the presence of input voltage and the

 

status of output voltage.

 

 

 

1-26

Page 40
Image 40
Motorola 3460 manual Replace the power module