Chapter 3 Tag Configuration
BridgeVIEW User Manual 3-40 © National Instruments Corporation
Table 3-10. Configuration Settings for Activity 3-1
Category Attribute Setting
General Tag N ame Product
Tag Group group1
Tag Description Volume of finished
product in liters
Connection Tag Access Input Only
Server Name Tanks Server
I/O Group ALL
Item tank2
Operations Update Deadband
(% of range) 1.00
Set Initial Value Enabled, 0.00
Log/Print Events Enabled
Log Data Enabled
Log Deadband
(% of range) 5.00
Log Resolution
(engineering units) 0.10
Scaling Engineering Unit Liters
Scaling <none>
Raw Full Scale 1000.00
Raw Zero Scale 0.00
Coerce to Range Disabled