7. Charger Set-Up

7. Charger Set-Up

This screen allows changes to the FLEXmax 80’s recharging voltage set points—Current Limit, Absorb and Float (for an explanation of battery charging, see pages 81-82):

The presently selected numerical value will have an arrow “ G ” to the left of it.

Pressing < Current Limit > selects the value to be changed.

You may need to re-enter the password to change these settings.

The default charger output current limit setting is 80 amps and is adjustable from 5-80 amps. An appropriate breaker must be used between the battery and the FLEXmax 80.

Change Absorbing and Float set points using this screen if the battery manufacturer’s recommenda- tions are different than the default values. Otherwise, see page 84 for suggested recharging voltage set points.

GCharger Aux Light EQ Misc Advanced Logging Stats

EXIT F G GO

Current Limit

G

80.0A

Absorbing

 

14.4V

Float

 

13.8V

EXIT I

-

+

From the MAIN screen, press 80.0A or Absorbing to move the "14.4V“ to the left of the Charger function and then press the <GO> soft key. This will open the Charger Set-Up screen.

Note: If a battery remote temperature sensor (RTS)

is used, set the ABSORB and FLOAT setting voltage based on a 25°C / 77°F setting. These are typically the manufacturer’s set points (always consult the battery

manufacturer’s recommendations). RTS compen- sated voltage values can be viewed in the Advanced

menu screen under the RTS Compensation heading. If an RTS is not in use, please see the Non-Battery Temperature Compensated System values (page 83) and adjust the ABSORB/FLOAT values accordingly.