FLEXmax 80 Internal Fan

The internal fan will only run when the internal temperature has reached approximately 112°F. The fan will continue running until the internal temperature is less than 104°F.

FLEXmax 80 is beeping

When the FLEXmax 80 is in Extended Play mode, the array is very hot, and the MPP is close to the battery voltage, or the nominal PV voltage is higher than the nominal battery voltage, beeping can occur. To disable the Extended Play feature, go to the MAIN Menu and press and hold the #1 soft key until the FLEXmax 80’s software version appears on the screen. Continue pressing the #1 soft key and press the #3 soft key at the same time until X Off displays on the screen. To reactivate Extended Play, repeat these steps and hold the #3 soft key until X On displays. Extended Play is meant to optimize the performance of a hot array, but isn’t critical to efficient FLEXmax 80 operations.

To enable/open the FLEXmax SELECT VERSION screens:

• Turn off the DC and array breakers

Press and hold the first and third soft keys

Turn on the battery breaker

Follow the SELECT VERSION screen instructions from the beginning of the manual

Rebooting the FLEXmax 80 like this will return all the values and set points to the factory defaults.

DC Breakers /

Battery Breaker

Press and hold the first and third soft keys

Figure 9

74

Page 75
Image 75
Outback Power Systems FLEXmax 80 Internal Fan, FLEXmax 80 is beeping, To enable/open the FLEXmax Select Version screens