LOW BATTERY DISCONNECT

AUX MODE

 

 

 

 

Low Batt Disconnect

 

 

 

 

Output: On

On

 

 

 

On

 

 

 

EXIT NEXT

SET MODE

 

 

 

Off

 

 

 

 

 

 

 

 

Auto

AUX MODE

Low Batt Disconnect

When the battery voltage falls below the disconnect volts, the AUX connected loads only are disconnected; the AUX connected loads only are connected when the battery voltage rises above the reconnect volts. To adjust these set points, press the <TIME> and <VOLT> soft keys.

Press the <TIME> and <VOLT> soft keys to adjust the set points.

EXIT

TIME VOLT

Delay Time Sec

01Timer 001

BACK - +

Press either the < - > or < + > soft key to adjust the delay time. This is the time period the FLEXmax 80 waits before either activating or deactivating the AUX MODE when either the disconnect or reconnect voltages are reached. When the low voltage occurs, the timer shows the seconds remaining before disconnecting. When the reconnect voltage is reached, the timer shows the user-determined time before connecting. Press the <BACK> soft key to return to the Low Batt Disconnect screen.