AUX modes in order of appearance on the FLEXmax 80 display:
• Vent Fan • PV Trigger • Error Output • Night Light • Float • Diversion Relay
• Diversion Solid State • Low Battery Disconnect • Remote
Note: All AUX functions can be manually activated in On, Off, or Auto mode. In Auto mode, the function will automatically activate when a
When an AUX MODE is in AUTO, 12VDC is available at the AUX terminals and a condition, such as a voltage set point, is met. Other modes can be programmed in lieu of the specific ones listed here, but the Vent Fan mode is most easily changed (e.g., to activate an alarm instead of a fan). Here are the default AUX modes:
•Vent Fan— when the Vent Fan voltage set point is exceeded, the vent fan will run for at least 15 seconds (the fan helps remove hydrogen from battery enclosure), even if the set point is exceeded for only a few seconds due to a surge. If the set point is exceeded for longer than 15 seconds, the fan will stay on until the voltage drops below the set point. It then takes 15 seconds before the fan shuts off. This is an optional external fan and not to be confused with the FLEXmax 80’s internal, thermally activated fan which cools the unit.
•PV
•Error
•Night
•
•Diversion
•Diversion Solid
•Low Batt
•
* These functions support AUX polarity.