ADVANCED MENU
Auto ReStart
MODE 2
EXIT NEXT MODE
ADVANCED MENU
Aux Polarity
G Active High | |
EXIT NEXT | MODE |
ADVANCED MENU
Aux Polarity
G Active Low | |
EXIT NEXT | MODE |
ADVANCED MENU
Reset to Defaults?
EXIT NEXT | RESET |
From the Auto Restart MODE 2 screen, press the <NEXT> soft key to view the Aux Polarity screen.
When the AUX function is ON, 12 volts is present at the AUX terminal; when it’s OFF, 0 volts are present at the terminal. Aux Polarity allows the user to reverse the availability of this voltage for the Night Light, PV Trigger, or Diversion Relay functions. In Active High, the user establishes certain conditions for these functions. Pressing the <MODE> soft key brings up the Active Low screen which allows the user to reverse these conditions.
In the Active Low zero voltage will be available for a function that in Active High would normally have voltage. When one of the three functions— Night Light, PV Trigger, or Diversion
EXAMPLE
AUX MODE | G |
| AUX MODE | G |
|
PV Trigger |
|
| PV Trigger |
|
|
Output: Off | Off |
| Output: Off | Off |
|
EXIT NEXT SET MODE |
| EXIT NEXT SET MODE |
| ||
|
|
|
|
| |
PV Trigger Active High |
| PV Trigger Active Low |
In this screen, a user can press the <RESET> soft key to return the FLEXmax 80 to the factory default settings.
(If you do not need to reset, press the <EXIT> soft key to return to the STATUS screen.)
52