AUX MODE

G

Diversion: Relay

 

EXIT

TIME VOLT

Hold

 

 

Delay

01.0

 

Time

00

 

seconds

 

BACK

-

+

DLY+

 

AUX MODE

G

Diversion: Relay

 

EXIT

TIME

VOLT

Absorb--Float--EQ

Relative Volts

0.000.2

BACK - + HYST

Press the <TIME> soft key to advance to the Time screen which allows the user to adjust the minimum time the AUX MODE is active after the battery voltage falls below the Hysteresis voltage.

Hold Time shows how long the AUX MODE stays active after the battery voltage has fallen below the HYST (Hysteresis) set point. The user can adjust the Hold Time from 0.1 to 25 seconds.

The Delay Time shows how long the battery voltage must be above the Relative Volts before the AUX MODE is activated. It can be adjusted from 0 to 24 seconds, but is rarely required. Pressing the <BACK> soft key returns to the AUX MODE Diversion: Relay TIME and VOLT screen.

Press the <VOLT> soft key.

Use this screen to establish the set points for starting and ending the AUX MODE relative to the Absorb, Float, and EQ voltages. The < - > and < + > soft keys set the Diversion set points. The <HYST> (Hysteresis) set point establishes when the AUX MODE becomes inactive after the battery voltage falls below the Relative Volts voltage minus the HYST value. After establishing these values, press the <BACK> soft key to return to the Diversion: Relay TIME and VOLT screen.

34

Page 35
Image 35
Outback Power Systems 80 user manual Diversion Relay, Hold Delay 01.0 Time Seconds, Back DLY+ AUX Mode, Back + Hyst