SOLA 4000 - PCB Description

1 UPS Control Logic

CPHC16 - S Front View

DIAGNOSTICS

Bypass

RS 232

RS 485

FIG. 1.8 illustrates the display, switches and connectors of the CPHC16 - S PCB which are accessible from the front.

7 segment display for diagnostics (see table below)

Manual transfer to bypass pushbutton

RS232 connector (male)

RS485 connector (female)

Priority

Indication

Diagnostics

 

 

 

1

8

E²PROM failure

 

 

 

2

F

Bypass Fuses Blown or IRE open

 

 

 

3

C

Phase failure

 

 

 

4

P

Incorrect phase rotation

 

 

 

5

Bypass square wave generation error

 

 

 

6

O

Output out of tolerance

 

 

 

7

L

Overload

 

 

 

8

4

Mains frequency out of tolerance

 

 

 

9

H

Mains voltage out of tolerance

 

 

 

10

6

Auxiliary power supply failure on the

SS/FY pcb

 

 

 

 

 

11

b

Bypass blocked

 

 

 

12

S

Bypass not synchronised

 

 

 

13

d

SSB failure

 

 

 

14

E

Bypass system not available

 

 

 

15

9

Missing or false bypass trip signal

 

 

 

16

7

EPO activated

 

 

 

17

U

IUG open

 

 

 

18

--

SSB on

 

 

 

In normal condition the display shows a red seg- ment rotating clockwise.If more than one alarm is present, only the one with the higher priority

is displayed.