Powerware SOLA 4000 manual Input Cables / Fuses, Mm²

Models: SOLA 4000

1 108
Download 108 pages 42.07 Kb
Page 22
Image 22

SOLA 4000 - Installation and Initial Start-Up

1 Installation

Version 1 SOLA 4000 with Common Input for

Rectifier and Bypass

Input Cables / Fuses

Type

 

Input

Input

earth

SOLA

 

cables

fuses

cable

4000

 

[mm²]

[A]

[mm²]

 

 

 

 

 

10

 

4x10

25

16

15

 

4x10

35

16

20

 

4x16

50

16

30

 

4x25

63

25

40

 

4x35

100

25

60

 

4x35

125

25

80

 

4x70

160

50

100

 

4x70

200

50

120

 

4x120

250

70

 

 

 

 

 

TAB.1.2.1

UPS input cables

 

and fuses, version 1

Output / Battery Cables and Max. Cur- rent Ratings for Battery Overcurr. pro- tection

Type

Battery

Output cables

Max. inv. input

SOLA

cables

[mm²]

current

4000

[mm²]

(Vdc=320V)

 

 

 

 

 

10

2x16

4x10

25

15

2x16

4x10

40

20

2x25

4x16

50

30

2x25

4x35

75

40

2x35

4x25

100

60

2x50

4x35

150

80

2x70

4x50

200

100

2x95

4x70

250

120

2x120

4 x120

300

 

 

 

 

TAB.1.2.2 UPS output cables and fuses, version 1

JUE 401265

22

Page 22
Image 22
Powerware SOLA 4000 manual Input Cables / Fuses, Mm²