SOLA 4000 - PCB Description

1 UPS Control Logic

CPHC16 - R Front View

DIAGNOSTICS

RESET MAX. Vdc

FIG. 1.2 illustrates the display, switches and connectors of the CPHC16 - R PCB which are accessible from the front.

-7 segment display for diagnostics (see table below)

-Reset max. Vdc pushbutton: press when the character "4" is displayed or the central segment is blinking.

-Reset Boost Charge Alarm

-Reset after EPO (V2.1)

RS 232

- RS232 connector (male)

RS 485

- RS485 connector (female)

Priority

Indication

Diagnostics

 

 

 

1

8

E²PROM failure

 

 

 

2

2

Fuse blown

 

 

 

3

C

Mains not OK

 

 

 

4

P

Wrong phase rotation

 

 

 

5

3

Overtemperature

 

 

 

6

4

Overvoltage

 

 

 

7

Ø

Pulse release missing

 

 

 

8

9

Rectifier failure

 

 

 

9

6

Fan failure

 

 

 

10

L

Overload

 

 

 

 

--

Boost charge

 

 

 

 

 

(when blinking)

 

 

Has left the boost

 

 

charge due to a given

 

"--"

time limit but the

 

battery was not

 

 

 

 

completely charged.

 

 

Reset with "RESET

 

 

max. Vdc" above.

 

 

 

JUE 401268

95

Page 95
Image 95