1 Installation
1.2 Electrical Installation
This equipment must be installed by qualified service person- nel.
Switch off IRP, IRE, IB, IUG, IBY circuit breakers to completely isolate the equipment.
Earth leakage protection: this device has high leakage current towards protective earthing. Earth leakage circuit breakers shouldn't be installed upstream from this equipment or a correct threshold should be set.
High leakage current - it is essential to connect the protective earth before connecting the power supply.
All primary power switches installed remotely from the UPS area must be fitted with the following label: "Isolate uninterruptible power supply (UPS) before working on this circuit".
General
All electrical connections must be made in accordance with local standards and all input terminals
If possible, install battery cables separately from other power cables in order to avoid possible RF interference. Before wiring, open all system switches (IRP, IRE, IBY, IUG) plus the battery switch (IB).