SOLA 4000 - Operating Panel

2 LED Indication

LOAD PERCENTAGE

The actual load is indicated by LEDs as a percentage of the nomi- nal load.

• All LEDs off

=> Actual load = 0 - 10%

Green LED 20% cont. illumin. => Actual load = 10 - 30%

Green LED 40% cont. illumin. => Actual load = 30 - 50%

Green LED 60% cont. illumin. => Actual load = 50 - 70%

Green LED 80% cont. illumin. => Actual load = 70 - 90%

Green LED 100% cont. illumin. => Actual load = 90 - 100%

Red LED 125% cont. illumin. => Actual load = 100 - 125%

-The UPS is in an overload condition.

-The buzzer is beeping continually and cannot be muted.

LED 29 COMMON ALARM

Red LED continually illuminated and BUZZER beeping fast = any of the following conditions:

-Inverter Failure

-Battery Switch Open

-Low Battery

-Rectifier Failure

-Paralleling Fault

-Inverter not synchronised (with the bypass supply or internal oscillator)

-Retransfer blocked

-Overtemperature

-Battery Test Failed

-Inverter not Feeding and bypass off (not active for hot- standby)

-Bypass system not available (but bypass of this unit is avail- able when more than one bypass is installed)

Yellow LED continually illuminated and BUZZER beeping slowly = any of the following conditions:

-Mains Failure (rectifier)

-Mains Failure (bypass)

-Battery Discharging

-Bypass not available

-Overload

-Load on Bypass (SSB closed)

-Inverter not synchronised (with the bypass supply )

-Auxiliary Alarm

Otherwise the LED is off

LED 30 BOOST CHARGE

Green LED on = Boost charge active

Otherwise LED is off.