SOLA 4000 - PCB Description

1 UPS Control Logic

P1 Freq.

Offset

P5 ΦT Volts

ICT-2 Front View

P4 ΦS Volts

P3 ΦR Volts

P2 Manual Test

LD5 Overload Φ

T

LD4 Overload Φ S

LD3 Overload Φ R

LD2 Pulse Release

LD1 Synch. OK

TP5

TP4 Inom= 6V

TP3 Inom= 4V ΦT

TP2 Inom= 4V ΦS

TP1 Inom= 4V ΦR

P8 Inom ΦT

P7 Inom ΦS

P6 Inom ΦR

-Proportional to the inv. voltage. 6V nominal inverter voltage

-Inv. voltage tolerance adjust for 6V at TP1 with nom. voltage

-Push to switch ON the inverter output static switch (SSI)

FIG. 1.4 illustrates the potentiometers, LEDs and test points of the ICT-2 PCB which are accessible from the front.

-Frequency offset adjustment (when synchronisation is blocked at TP5)

-Inverter voltage adjustment phase T

-Inverter voltage adjustment phase S

-Inverter voltage adjustment phase R

-Inverter voltage adjustment during test operation (jumpers JP1, JP2, JP3 in position 2,3)

-Overload on phase T: red LED is illuminated

-Overload on phase S: red LED is illuminated

-Overload on phase R: red LED is illuminated

-Pulse release: green LED is illuminated

-Synchronisation OK: green LED is illuminated

-Synchronisation block

-Test point: test voltage = 6Vdc at full load

-Test point: test voltage = 4Vdc at full load on phase T

-Test point: test voltage = 4Vdc at full load on phase S

JUE 401268

98

Page 98
Image 98