Powerware SOLA 4000 manual System Data, Sola 4000 Technical Data

Models: SOLA 4000

1 108
Download 108 pages 42.07 Kb
Page 105
Image 105

SOLA 4000 - Technical Data

1 System Data

Technical Data / System Data

 

 

 

 

 

 

Type SOLA 4000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

15

 

20

30

 

40

60

 

80

100

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System configuration

 

On-line (double conversion)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal input voltage

 

3Ph+N x 380 ÷ 415 V Tolerance: ± 10%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal input frequency

 

50 / 60 Hz

Tolerance: ± 10%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal output voltage

 

380 / 400 / 415 Vac (adjustable)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal output frequency

 

50 / 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output voltage distortion (THD) linear load

 

< 1%

 

 

 

 

 

 

 

 

 

 

 

 

 

non linear load at 100% of Pn and C.F. = 3

< 4%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output voltage regulation with load between 0 and

± 1% (balanced or unbalanced)

 

 

 

 

 

 

100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output frequency regulation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- synchronisation with mains

 

± 0,5 / 1 / 2 Hz (selectable with software)

 

 

 

 

- free running

 

± 0,01 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated output power, power factor = 0.8

[kVA]

10

 

15

 

20

30

 

40

60

 

80

100

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated output power, power factor = 1

[kW]

8

 

12

 

16

24

 

32

48

 

64

80

 

96

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Efficiency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- 50% load

[%]

> 88

 

> 88

 

> 88

> 88

 

> 90

> 90

 

> 90

> 90

 

> 90

- 100% load

[%]

> 90

 

> 90

 

> 90

> 90

 

> 91

> 91

 

> 91

> 91

 

> 91

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Losses at nominal load, charged battery <= [kW]

0,8

 

1,2

 

1,6

2,4

 

3,2

4,8

 

6,4

8

 

9,6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Inverter

 

125 % 10 minutes, 150 % 1 minute

 

 

 

 

 

 

- Static bypass switch (SSB)

 

2000 % 20 msec, 200 % 1 minute, 150 % continuous

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Permissible inverter output voltage variation for

± 10%

 

 

 

 

 

 

 

 

 

 

 

 

bypass switching

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Design standards

 

IEC 146-4, EN50091-1, IEC 950

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Insulation test for 60s

 

2,0 kV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cabinet protection

 

IP 20 acc. to IEC 529, IEC 944 (excl. air exit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- operating temperature

 

0 .. 40 °C

 

 

 

 

 

 

 

 

 

 

 

- storage temperature

 

0 .. 85 °C (excluding battery)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Permissible relative humidity

 

< 95 % UR (non condensing)

 

 

 

 

 

 

 

 

 

Maximum altitude above sea level at full load

< 2000 m. Higher altitudes require power derating or

 

 

 

increased cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

RFI suppression

 

EMC standard satisfied with EN50091-2 (1995) class A -

 

 

 

IEC801-2 - IEC801-3 - IEC801-4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Audible noise level at 1 meter

<= (dBA)

58

 

58

 

58

58

 

60

60

 

61

61

 

62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIG. 1.1 - System Data

JUE 401269

105

Page 105
Image 105
Powerware SOLA 4000 manual System Data, Sola 4000 Technical Data