SOLA 4000 - Installation and Initial Start-Up
2 Initial Start-Up
no: | The difference is probably due to distortion of the mains |
| voltage (the inverter voltage is an almost perfect |
| sinewave) |
| Continue with G |
yes: |
| Continue with G |
G: Static Switch Commutation Check | • | COMMUTATION TO THE BYPASS |
|
| Press the pushbutton on the |
|
| The static switch SSB will switch on and SSI will switch off, as |
|
| indicated on the front panel and on the SS/FY pcb (red LEDs). |
| • | COMMUTATION TO INVERTER |
|
| Press the pushbutton PB3 at the bottom of the ICP pcb. The |
|
| static switch SSI will switch on and SSB will switch off, as |
|
| indicated on the front panel and the SS/FY pcb (green LEDs). |
H: Battery Charging Current Limitation | • Connect the load and open IRP. | |
Check | ||
| The load is now supplied only by the batteries. | |
| • | Discharge the batteries for about 2 minutes at nominal UPS |
|
| load or longer if the connected load is smaller than nominal |
|
| UPS load |
| • | Close IRP again. |
| • | After 30 seconds, measure the battery voltage. |
? Is the battery voltage lower than the set floating charge voltage?
no The rectifier is not yet in battery current limitation. In order to check the battery current limitation you must discharge the batteries for a longer period.
• Return to H.
yes The battery current limitation can now be checked according to the battery installed. Standard setting is 10% of the battery capacity.
•Measure the battery recharging current with a dc
?Is this approximately 10% of the battery Ah capacity?
no Check the settings of the dipswitch S1 on the CPHC16
•Return to H.
yes THE