SOLA 4000 - Installation and Initial Start-Up

2 Initial Start-Up

no:

The difference is probably due to distortion of the mains

 

voltage (the inverter voltage is an almost perfect

 

sinewave)

 

Continue with G

yes:

 

Continue with G

G: Static Switch Commutation Check

COMMUTATION TO THE BYPASS

 

 

Press the pushbutton on the CPHC16-S pcb for the bypass.

 

 

The static switch SSB will switch on and SSI will switch off, as

 

 

indicated on the front panel and on the SS/FY pcb (red LEDs).

 

COMMUTATION TO INVERTER

 

 

Press the pushbutton PB3 at the bottom of the ICP pcb. The

 

 

static switch SSI will switch on and SSB will switch off, as

 

 

indicated on the front panel and the SS/FY pcb (green LEDs).

H: Battery Charging Current Limitation

• Connect the load and open IRP.

Check

 

The load is now supplied only by the batteries.

 

Discharge the batteries for about 2 minutes at nominal UPS

 

 

load or longer if the connected load is smaller than nominal

 

 

UPS load

 

Close IRP again.

 

After 30 seconds, measure the battery voltage.

? Is the battery voltage lower than the set floating charge voltage?

no The rectifier is not yet in battery current limitation. In order to check the battery current limitation you must discharge the batteries for a longer period.

• Return to H.

yes The battery current limitation can now be checked according to the battery installed. Standard setting is 10% of the battery capacity.

Measure the battery recharging current with a dc clip-on amme- ter.

?Is this approximately 10% of the battery Ah capacity?

no Check the settings of the dipswitch S1 on the CPHC16 -R pcb for the rectifier according to JUE400899 programming of PCBs (V2.0 or later). Otherwise, the battery charging current may need to be adjusted using the RS232 connector on the CPHC16-R pcb and a portable computer. This must be performed by first discharging the battery by switching off IRP, connecting the PC and adjusting the charging current. The battery must remain connected through- out the procedure.

Return to H.

yes THE START-UP PROCEDURE HAS BEEN SUCCESSFULLY COMPLETED NOW.