Powerware SOLA 4000 manual Installation of External Batteries

Models: SOLA 4000

1 108
Download 108 pages 42.07 Kb
Page 44
Image 44

SOLA 4000 - Installation and Initial Start-Up

1 Installation

1.12.2 Installation of External Batteries

External Battery (38 Ah) Installation 38 Ah external batteries are installed in a B3/38 battery cabinet. To assemble the battery cabinet:

Place four battery blocks on the trays of the first level (see FIG. 1.12.2).

Place six battery blocks on the trays of the second and third levels (see FIG. 1.12.3).

Interconnect the blocks in series (block 1 / negative pole ==> block 2 / positive pole,....)

Warning: after assembly there is a voltage of 48 V on the first level, and 72 V on the second and third levels.

If necessary secure with strapping (against vibrations).

Insert the trays into the battery cabinet as shown in FIG. 1.12.4

FIG. 1.12.3 B3/38: battery trays in the second and the third level

FIG. 1.12.4 Battery cabinet B3/38

JUE 401265

44

Page 44
Image 44
Powerware SOLA 4000 manual Installation of External Batteries, 12.3 B3/38 battery trays in the second and the third level