1 UPS Control Logic

In normal condition the display shows a red seg- ment rotating clockwise. During the starting phase, a blinking central segment "-" is displayed. During parameter acquisition through the serial interface, the character "A" is displayed. If more than one alarm is present, only the one with the higher priority is displayed.

1.3 Inverter

The inverter control logic consists of three PCBs (four for parallel systems).

ICP Inverter control

control for the inverter static switch (SSI)

temperature monitoring

inverter monitoring and protection

hot-standby control

quartz oscillator

fan monitoring

inverter electronic power supply monitor

ICT-2Inverter regulation

inverter output voltage regulation

inverter output current limitation

short-circuit protection

inverter soft start control

inverter-bypass synchronisation

inverter-oscillator synchronisation

synchronisation monitor:

IPS - 500 Inverter electronic power supply

inverter electronic power supply

inverter input voltage monitoring

generation of the battery-discharging alarm

JUE 401268