SOLA 4000 - Installation and Initial Start-Up

1 Installation

1.6 Remote Emergency Power off

A Remote Emergency Power Off may be connected to the system. The connection terminals are M4 Pin 5 and Pin 6, using a nor- mally-open, voltage-free contact as a pushbutton.(See FIG. 1.6.1. and FIG 1.6.2.)

FIG. 1.6.1 Connection of Remote EPO with N.C. contact

FIG. 1.6.2 Connection of Remote EPO with N.O. contact

Note 1: The cable used must be twisted pair, with a total shield. This shield must be grounded at one end (the cabinet of the UPS may be used).

Note 2: For Hot-Standby or parallel systems, it is sufficient to feed one contact into one unit only, however they may be connected in parallel at M4 (of IBYBP-CP) Pin5 and Pin 6 for all units (N/O) only or series for (N/C).

Note 3: To completely isolate the UPS system from all voltage with the emergency power off (EPO), it is necessary to install trippable circuit breaker on the input supply (to terminals 1-L1, 1-L2, 1-L3 and 4-L1, 4-L2, 4-L3 and 4-N if installed).

The trip coil is then connected to the terminal M1 on the CPU/NCP pcb located inside the front door of the cabinet. A normally open or normally closed voltage-free contact is available.

Note 4: The N.C. contact can only be used for IBYBP-CP motherboards in rev. 0A and following.

FIG. 1.6.3 Connection of Remote Emergency Power Off - Input and battery circuit breaker trip circuit.

Nominal Rating of Contacts

125 V

0,5 A

60 W

 

 

 

 

30 V

2 A

60 W

 

 

 

 

TAB. 1.6.1 Nominal Rating of contacts for the input breaker trip circuit.

JUE 401265

32

Page 32
Image 32
Powerware SOLA 4000 manual Remote Emergency Power off, Connection of Remote EPO with N.C. contact