SOLA 4000 - Installation and Initial Start-Up
1 Installation
1.8 Common Alarm Contacts
As a standard feature, contacts are provided for a remote common alarm.The connector is located on the control p.c.b for the front operating panel (CPU/NCP), located inside the front door of the UPS.
FIG. 1.8.1 Connection of Remote Common Alarm
Nominal Rating of Contacts
125 V | ≅ | 0,5 A | 60 W |
|
|
|
|
30 V | ≅ | 2 A | 60 W |
|
|
|
|
TAB. 1.8.1 Nominal Rating of contacts for the common alarm.
Note 1: As an option a pcb
A Remote panel may also be purchased with identical functions to the front operating panel.
Note 2: To achieve a single common alarm for parallel or hot- standby units, the contacts of each unit may be interconnected in parallel (normally - open) or series (normally - closed).
1.9 Remote Reset
The UPS system may be reset remotely with the connection of contacts ( a
FIG.1.9.1 Connection of Remote Reset
Note: The cable used must be twisted pair, with a total shield.
This shield must be grounded at one end (the cabinet of the
UPS may be used).