SOLA 4000 - Installation and Initial Start-Up

1 Installation

1.8 Common Alarm Contacts

As a standard feature, contacts are provided for a remote common alarm.The connector is located on the control p.c.b for the front operating panel (CPU/NCP), located inside the front door of the UPS.

FIG. 1.8.1 Connection of Remote Common Alarm

Nominal Rating of Contacts

125 V

0,5 A

60 W

 

 

 

 

30 V

2 A

60 W

 

 

 

 

TAB. 1.8.1 Nominal Rating of contacts for the common alarm.

Note 1: As an option a pcb CP-NET is available, providing more contacts, compatible with most common configurations (eg AS400, Novell etc.)

A Remote panel may also be purchased with identical functions to the front operating panel.

Note 2: To achieve a single common alarm for parallel or hot- standby units, the contacts of each unit may be interconnected in parallel (normally - open) or series (normally - closed).

1.9 Remote Reset

The UPS system may be reset remotely with the connection of contacts ( a push-button) to the terminal M4 as shown:

FIG.1.9.1 Connection of Remote Reset

Note: The cable used must be twisted pair, with a total shield.

This shield must be grounded at one end (the cabinet of the

UPS may be used).

JUE 401265

34

Page 34
Image 34
Powerware SOLA 4000 manual Common Alarm Contacts, Remote Reset