SOLA 4000 - Operating Panel

2 LED Indication

LED 18 LOAD FED BY BYPASS POWER SUPPLY

Yellow LED is continually illuminated = Load fed by static bypass

Otherwise LED is off.

LED 19 LOAD IS SUPPLIED

Green LED is continually illuminated = Load fed either by inverter or by static bypass and IUG is closed

Otherwise LED is off.

LED 27 BATTERY TEST

This test is only performed if the batteries are fully charged. Other- wise the test is skipped and performed in the following month.

LED off = BATTERY TEST function not active

Green LED is continually illuminated = BATTERY TEST func- tion activated, but UPS is not performing the test

Green LED flashing slowly = BATTERY TEST running

Red LED flashing fast + BUZZER beeping fast = BATTERY TEST failed. Test battery capacity.

LED 28 E.P.O.

Red LED is continually illuminated = E.P.O. has been activated Note: For parallel and hot-standby systems, EPO may be have been activated at any unit.

LED 26 STATIC SWITCH

Green LED continually illuminated = Bypass available

Green LED flashing = Bypass not synchronised but the mains is OK

LED off = Mains not OK

LEDs BATTERY INDICATOR

a)During the charging phase (green LED L5 ON)

Green LEDs continuously illuminated indicate the actual battery autonomy as a percentage of the nominal battery autonomy, depending on the actual load and battery charging status.

b)During the discharging phase (yellow LED 4 ON)

If, during the discharging phase, the actual battery autonomy goes below 20% autonomy, the system signals the alarm "Low Battery ".

-The BUZZER beeps continually.

-The colour of the "battery indicator" LEDs changes from green to red.

The actual autonomy is signalled by the flashing of the corre- sponding LED.

When the LED corresponding to 0% autonomy starts flashing:

-The buzzer beeps continually and cannot be muted.

-The inverter will cease to operate soon.

JUE 401267

79

Page 79
Image 79
Powerware SOLA 4000 manual LED 28 E.P.O, LEDs Battery Indicator