SOLA 4000 - Operating Panel

4 Panel Settings

4 PANEL SETTINGS

4.1 DIP Switch Settings

With the DIP switches SW1 and SW2 on the CPU/NCP pcb inside the front door , the operating parameters can be set according to actual conditions.

Note: The following settings apply only with the software V2.0 or later.

DIP Switch SW1

Dip 1

Dip 2

Dip 3

Dip 4

UPS RATING

(KVA)

 

 

 

 

 

 

 

 

 

OFF

OFF

OFF

OFF

10

 

 

 

 

 

ON

OFF

OFF

OFF

15

 

 

 

 

 

OFF

ON

OFF

OFF

20

 

 

 

 

 

ON

ON

OFF

OFF

30

 

 

 

 

 

OFF

OFF

ON

OFF

40

 

 

 

 

 

ON

OFF

ON

OFF

60

 

 

 

 

 

OFF

ON

ON

OFF

80

 

 

 

 

 

ON

ON

ON

OFF

100

 

 

 

 

 

OFF

OFF

OFF

ON

120

 

 

 

 

 

TAB. 4.1 - Setting of SW1 - UPS rating

DIP Switch SW1

DIP 5

CONFIGURATION

 

 

OFF

Not Hot-standby

 

 

ON

Hot-Standby

 

 

DIP 6

BYPASS - LINE

 

 

OFF

Installed

 

 

ON

Not installed

 

 

TAB. 4.2 - Setting of SW1

DIP Switch SW1

Nominal Voltage

DIP 7

DIP 8

Vnom

 

 

 

OFF

OFF

120

 

 

 

ON

OFF

220

 

 

 

OFF

ON

230

 

 

 

ON

ON

240

 

 

 

TAB. 4.3 - Setting of SW1 Nominal Voltage