SOLA 4000 - PCB Description

1 UPS Control Logic

1.4 Bypass

The bypass static switch control logic consists of two PCBs.

IF/PS - S Bypass monitoring and power supply

bypass electronic power supply

mains voltage sensing

CPHC16 - S Bypass control

switching control of the static bypass switch SSB

interface with the inverter or multiple inverters

mains frequency monitoring

mains voltage and phase rotation monitoring

generation of synchronisation signal

interface with multiple static bypasses

UPS output voltage monitoring

majority control for multiple static bypasses (parallel and hot standby systems)

synchronisation monitor: mains - UPS output

JUE 401268

101

Page 101
Image 101
Powerware SOLA 4000 manual Bypass