SOLA 4000 - Technical Data

2 Rectifier Data

Technical Data / Rectifier Data

 

 

 

 

Type SOLA 4000

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

15

20

30

40

60

80

100

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input voltage

 

refer to system data

 

 

 

 

 

 

Tolerance

 

refer to system data

 

 

 

 

 

 

with reduced output (DC) voltage

 

-20 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input frequency

 

refer to system data

 

 

 

 

 

 

Tolerance

 

± 10 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated input power with charged battery

 

 

 

 

 

 

 

 

 

 

-

[kVA]

10,8

 

16

21,3

32

42,7

64,1

84,8

106

127,4

 

 

 

 

 

 

 

 

 

 

 

Rated input current with charged battery

 

 

 

 

 

 

 

 

 

 

(380 V)

[A]

16,4

 

24,6

32,7

49,2

65

97,5

128,5

160,7

193

 

 

 

 

 

 

 

 

 

 

 

 

Maximum input power

 

 

 

 

 

 

 

 

 

 

 

-

[kVA]

13,5

 

20

26,9

39,8

53,5

80

105

132

158

 

 

 

 

 

 

 

 

 

 

 

Maximum input current, input voltage = 380 V

 

 

 

 

 

 

 

 

 

 

-

[A]

20,5

 

30,8

40,8

61,2

81,5

122

160,5

201

241

 

 

 

 

 

 

 

 

 

 

 

 

Input power factor

 

~ 0,83 lag.

 

 

 

 

 

 

 

( nom. load, input voltage = 380V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output control characteristics

 

I/U characteristic, boost charge possible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated output voltage

 

 

 

 

 

 

 

 

 

 

 

- Lead-Acid batteries

 

432 V/DC

 

 

 

 

 

 

 

- Ni-Cd batteries

 

436 V/DC

(depending on number of cells)

 

 

 

 

 

 

 

 

 

 

 

 

Soft start

 

~ 10 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Floating voltage regulation with load between 0

1 %

 

 

 

 

 

 

 

 

 

and 100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output voltage ripple with battery disconnected

RMS 1 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. batt. recharging current with nom. load

5

 

7,5

10

15

20

30

40

50

60

-

[A]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Complies with battery manufacturer's recommendations,

 

Battery charging current limitation

 

standard setting approximately 10% of rated battery capacity

 

 

 

 

 

 

 

 

 

 

 

 

IG. 2.1 - Rectifier Data

JUE 401269

106

Page 106
Image 106
Powerware SOLA 4000 manual Rectifier Data